ATS Designers Guide
80
Current cons. mA
Device
Connected
Expansion
Description
Max. Typical
Required
voltage V
Notes
ATS1156 -
System keypad, 3 system status LED, metal
housing, with magnetic card reader (ACT600)
45 39 7,35
Each LED lit add: +9mA;
Card swipe add: +5mA.
- Wiegand reader interface, PCB only 45 32
ATS1170
ATS1190
Wiegand reader interface, with proximity reader
connected
95 65
9,6
ATS1190 -
ATS proximity Smart Card reader (do not require
interface)
50 29 7,99
ATS1192 -
ATS proximity Smart Card reader (do not require
interface), vandal resistant housing
50 29 7,99
ATS1202 -
Zone expansion module 8 input for control panel
and DGP, PCB
10 9
- Zone expansion DGP – 8 inputs and 8 outputs 53 50 6,73 Sends „Low Voltage” message at 10,5VDC
ATS1810 ATS1210/11 with 4 relays module connected 130 70 9,6
All relays active. Minimum voltage to activate relays
10,3VDC. Pooling continues up to 5,5VDC.
ATS1811 ATS1210/11 with 8 relays module connected 225 110 9,6
All relays active. Minimum voltage to activate relays
10,1VDC. Pooling continues up to 5,5VDC.
ATS1210/11
ATS1820 ATS1210/11 with 16OC module connected 90 38 6,73 All outputs active without any additional load.
ATS1220 - Zone expansion DGP – 4 inputs 53 45 6,73
ATS1230 -
Zone expander DGP - wireless devices receiver,
433MHz freq. Up to 32 detectors and 16 keyfobs
39 7,48
-
Zone expander DGP – addressable devices with
Point ID bus. Up to 32 devices.
53 50 9,5
Without Point ID load, no addressable devices
connected
ATS1290
PID bus
A
TS1290 with PID bus connected with max. load of
512UL
154 154 9,5
PID bus with maximum specified load of 512UL (UL
Unit Load)