60 ATS Designers Guide
Table 4-4 Available DGP modules and their expansions.
Zones Outputs Remarks Expansion
MBC ATS1202 ATS1810 ATS1811 ATS1820
ATS1201 8 3x8 2x4 2x8 1x16 Max outputs 16
ATS1203 8 3x8 2x4 4x8 2x16 Max outputs 32
ATS1210/11 8 2x4 2x8 1x16
ATS1220 4
ATS1290 32
ATS1230 32
The housing does not
allow installation of
additional expansions ,
device without a power
supply.
Planning for maximum DGP expansion the maximum system capacity – 256 zones- can
be achieved using 7 DGP modules. In an opposite case – using the mentioned 4 zone
DGP – after installing all possible DGP modules – 15 – all the expansions would make
total of 60 alarm zones.
4.2.1.2 Outputs
A similar rule is valid for the division of the system output address space. The output
addresses for a given DGP are defined by it’s address – number – in the system. DGP
can support a maximum of 16 outputs, which is the same as it’s assigned zone address
space. The control panel can support all the outputs, but due to power supply limits the
number is capped at 150. A higher number of outputs can be made available by installing
an additional power source.
Each system output is limited by a timezone. The system supports 16 areas, and for each
one a separate external and internal siren. The ATS1201 DGP is equipped with
dedicated, monitored siren output, addressed like the rest of the system outputs.
Table 4-5 Alarm zone and output addressing in the ATS system.
Input Range Output Range DGP Address Remarks
1-16 1-16 16 (CP) Control panel alarm zones
17-32 17-32 1
33-48 33-48 2
49-64 49-64 3
65-80 65-80 4
81-96 81-96 5
97-112 97-112 6
113-128 113-128 7
129-144 129-144 8
145-160 145-160 9
161-176 161-176 10
177-192 177-192 11
193-208 193-208 12
209-224 209-224 13
225-240 225-240 14
241-256 241-255 15 Output 256 is not available
4.2.1.3 Sirens
Each of the 16 areas can have two signallers defined: internal and external. Configuring
the sirens in the system is the same as configuring the outputs: the event flag is assigned
to an output. Apart from the control panel, the siren outputs are available in the ATS1201,
ATS1203 and ATS1250/60 DGP. The signaller outputs are protected by fuses and
monitored. By default the system is programmed to activate all external sirens in case of
an alarm in any area.